EasyManua.ls Logo

Allen-Bradley ControlLogix - From the Network Menu, Select Save as

Allen-Bradley ControlLogix
203 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1756-6.5.3 - December 1999
Logix5550 Controller to PLC-5C: Scheduled Communications 6-13
The Receive Scheduled Message configuration window will appear:
5. Enter the following parameters and click on OK.
A new configuration line in blue text will appear:
6. Click on the AutoMap All Entries button.
Input data will be mapped to a PLC5 file (e.g., N9:0).
7. From the Network menu, select Save.
In this field Enter
Node Number 1
Slot Number 0
Tag
produced_data
(1)
(1)
This is the name of the tag created in RSLogix 5000.
Requested Packet Interval (use default)
Message Size 2 (for DINT)
This new configuration line will appear.
For two-way communication
you can also configure the
PLC-5C to send messages to the
Logix5550 controller at this
time. See chapter 8 for details.
Input data mapped to N9:0

Table of Contents

Other manuals for Allen-Bradley ControlLogix

Related product manuals