1756-6.5.3 - December 1999
2-2 Installing the ControlNet Network
Installing the 1784-KTCX15
Communication Interface Card
Perform the following steps to install the 1784-KTCX15 card in your
personal computer.
1. Set the card’s base memory address location on switches S1 and S2.
2. Set the card’s base I/O space address location on switch S3.
We used the following settings:
Important:When deciding which addresses to use, remember that each
card in your computer must have a unique base memory
address and a unique base I/O space memory address. If
another card in the host computer is using one or both of the
selected addresses, you must change the card’s switch settings
to an available address.
3. Insert the card in a vacant 16- or 32-bit ISA/EISA expansion slot.
For detailed information on
installing the 1784-KTCX15,
refer to the ControlNet
Communication Interface
Card Installation Instructions,
publication number
1784-5.33.
Base I/O Space Address 240
Base Memory Address D000:000
Address 240
Consult with your IT/PC support group to find out if it is necessary to
change any of your computers memory address or IRQ settings.

Table of Contents

Other manuals for Allen-Bradley ControlLogix

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley ControlLogix and is the answer not in the manual?

Allen-Bradley ControlLogix Specifications

General IconGeneral
CommunicationEtherNet/IP, ControlNet, DeviceNet, DH+
I/O CapacityUp to 128, 000 I/O points (varies by configuration)
RedundancySupported (with specific modules)
Programming SoftwareRockwell Automation Studio 5000 Logix Designer
Operating Temperature0°C to 60°C (32°F to 140°F)
Programming LanguagesLadder Logic, Function Block Diagram, Structured Text, Sequential Function Chart
ModularityYes
CertificationsUL, CE
Processor TypeMultiple options available, including standard, safety, and extreme environment processors
Power SupplyMultiple options available, including standard and redundant power supplies with various voltage ranges (e.g., 24V DC, 120/240V AC)