7-21
Chapter 7. PARAMETER SETUP
maticre-adjustmenthasendedsuccessfullyorwhenthepower
hasbeenreset.
- Fullyclosedcount-fullyopencount<500
- Fullyclosedcount>fullyopencount
- Timefromfullyclosedtofullyopenislessthan5s
- MFBdisconnectedalarm(
A L 1 0
,
A L 1 1
)occurscontinu-
ouslyorfrequently
- ThetimetakenfortheMFBcounttostabilizeexceeds5min
- FaultywiringofMFBorswitchingrelay
(However,notethatallfaultywiringcannotbedetectedas
anerror.)
.-t
(motor valve opening adjustment fully open/closed time)
When
.-C
issetto2,thesettimeistakenasthebaseforallopera-
tions.Enterthetimecorrectlyin0.1sunits.