7-36
Chapter 7. PARAMETER SETUP
No. Item Code Item
Factory
Setting
User
Setting
Setting
33
E
t
.
t
5
T5 event type 50
PV type events
0: PV direct
1: PV reverse
2: Deviation direct
3: Deviation reverse
4: Absolute value deviation1 direct
5: Absolute value deviation1 reverse
6: SP direct
7: SP reverse
8: MV direct
9: MV reverse
10: MFB direct
11: MFB reverse
12 to 49: NOP
Time events
50: T ime event
51 to 99: NOP
Controller status events
100: RUN+HOLD+FAST+END
101: R E A DY
102: RUN
103: HOLD
104: FAST
105: END
106: G.Soak standby
107: M A NUAL
108: Auto-tuning executing
109: Constant-value operation
110: MFB estimated position control
111: Sum of all alarms
112: PV range alarm
113: Controller alarm
114: Low battery voltage
115: Console setup in progress
116: Loader setup in progress
117: ADV (ON time 1s)
118 to 124: NOP
125: Pr o gr am en d
126 to 129: NOP
[Note]
Setting can be changed only in READY
mode.