9-18
Chapter 9. MAINTENANCE & TROUBLESHOOTING
(14) Tightenthelockscrewwhileslightlypushinginthecontroller’s
console.Takecarenottoovertightenthescrew.
(15) TurnthecontrollerON,andmakesurethattheBATLEDisout.
 
Note
•
Thefollowingservesasageneralguidelineforwhentoreplacethe
battery:
About3yearswhenusingthecontrollerunderstandardoperating
conditions(operatingtemperature:23±2°C)withthecontroller
ON
About10yearswhenusingthecontrollerunderstandardoperating
conditions(operatingtemperature:23±2°C)withthecontroller
OFF
Usingthecontrollerinahigheroperatingtemperaturewillshorten
itsservicelife.
•
SetupsareheldinmemoryeveniftheBATLEDisblinking.
•
Thecontrolleroperatesinoneoftwowayswhenmemorycontents
aredamaged.
(1) “
G
.R
E
S
”isdisplayedwhenthecontrolleristurnedONand
regularoperationisnotstarted.
(Ifthishappens,press
ENT
toexecuteageneralreset.This
restoresparametersetupstofactorysettingsandclearsthe
programsetup.)
(2) Regularoperationisstartedwhenthecontrolleristurned
ON,andoneorbothofalarmcodes
A
L
q
6
and/or
A
L
q
7
is
displayed.