5-6
Chapter 5. FUNCTIONS
Controller status events
ControllerstatuseventsareturnedONandOFFaccordingtothe
controllermode,alarmstatusandotherstatuses.
Thoughtheeventstandbyfunctiondoesnotfunction,theONdelay
functiondoes.
Eventsettingvalues(operatingpoint),hysteresisandeventstandby
arenotset.
• Basicoperations
Thefollowingbasicoperationtypesareprovided:
RUN+HOLD+FAST+END
READY
RUN
HOLD
FAST
END
G.Soakstandby
MANUAL
Auto-tuningexecuting
Constant-valueoperation
MFBestimatedpositioncontrol,sumofallalarms
PVrangealarm
Controlleralarms
Lowbatteryvoltage
Consolesetupinprogress
Loadersetupinprogress
ADV
Programend
WhentheDCP31reachesthestatedesignatedbytheeventtype,
theeventisturnedON.Otherwise,theeventisOFF.
• Alarms
AlarmsaredividedintoPVrangealarmgroups(alarmcodeNos.
01to16)andcontrolleralarmgroups(alarmcodeNos.70to99,
andlowbatteryvoltage).
Whentheeventtypeissettothesumofallalarms,theevent
turnsONifanyoneofthealarmsoccurs.