5-7
Chapter 5. FUNCTIONS
WhentheeventtypeissettoPVrangealarm,theeventturnsON
ifanyoneofthealarmsinthePVrangealarmgroupoccurs.
Whentheeventtypeissettocontrolleralarm,theeventturnsON
ifanyoneofthealarmsinthecontrolleralarmgroupoccurs.
ADV
ThisisONfor1safterexecutingprogramadvance.TheeventON
delayisdisabledandadelayisnotapplied.
• Programend
WhentheDCP31automatically(includingADV)reachesthe
READYmodefromprogramoperationstatus(RUN,HOLD,
FAST)withoutperformingRESEToperation,theeventisturned
ON.WhenshiftingfromENDmodetoREADYmode,theevent
isnotturnedONasRESEToperationisrequired.
Thiseventiscancelled(ON→OFF)whenoneofthefollowing
conditionsissatisfied:
•WhenRESEToperationisperformed.
•WhenshiftingfromREADYtoRUNmode.
•Whenpowerisagainsupplied.