Auto (Autolearning - Automatic enrolling)
The Auto option from the PROGRAMMING menu will allow you to enrol
the loop devices and the RS485 network devices automatically.
+
Autolearning (enrolling) must be done during the installation phase and af-
ter changes to the loop and network configurations, bell outputs and Tele-
com module.
+
Ensure that the SAME ADDRESS LED is OFF before starting.
Ø Select the Network option from the SYSTEM menu then configure the
FireClass200 as the Master panel. Otherwise, the Master panel will be un-
able to communicate with the system repeater and slave panels).
Ø Auto-learning does not modify the programmed parameters.
1. Select the Auto option from the PRO-
GRAMMING menu (press 1).
2. The control panel will search Loop 1 ...
3. then Loop 2 ...
4. and finally the RS485 network.
5a. When the Auto-learning phase ends on a
SLAVE panel, the display will show ...
1=Auto 2=Devices
3=PassWD 4=MesINI
5=Zones 6=Opt 7=Sys
8=Ver 9=Def Ø=Tel
Autolearning
searching on:
LOOP 1
please wait....
Autolearning
searching on:
LOOP 2
please wait....
Autolearning
searching on:
NET
please wait....
Analysis connections
1)LOOP 1
2)LOOP 2
3)NET not supported
40 Analogue Fire Control Panel FireClass200