OVERVIEW
Access Levels
The FireClass200 Access Levels filter system control as follows.
Level 1 All persons can view the system status through the Plexiglas window.
Level 2A Only authorized key holders can open the cabinet door access the manual
commands (RESET, SILENCE and LOGGER).
Level 2B Only authorized User PINs (1 to 5 digit codes) can Enable/Disable the
Loop devices, Bell Outputs, Software Zones and Network devices.
Level 3A Only the Installer PIN (1 to 5 digit code) can access the parameter pro-
gramming phase.
Level 3B 0nly authorized personnel are allowed to open the cabinet (remove the screws
and open the control panel door) for maintenance work (change the battery,
replace fuses, etc).
Level 4 Only the manufacturer is allowed to open the cabinet (remove the screws
and open the control panel door) for PCB repair work (replace compo-
nents, etc.).
Main Features
Day/Night The FireClass200 can operate in Day or Night Mode.
If the system is silenced during Day Mode, SILENCE status will be held
until the system is unsilenced (i.e. unless new alarms or faults occur).
If the system is silenced during DAY Mode, SILENCE status will be held
until the system is unsilenced (i.e. unless new alarms or faults occur).Si-
lence will be enabled until the SILENCE button is pressed again.
If the system is silenced during NIGHT Mode, SILENCE status will be for
the preset time (accepted values: 30 seconds to 30 minutes).
This system provides Automatic Alarm Threshold variation.
The preset Alarm Threshold of analogue detectors will be increased during
Day Mode, in order to avoid false alarms caused by persons (cigarette
smoke, etc.) in the protected ambient.