Silence mode
The control panel SILENCE button will disable all Outputs in ALARM
status (Bell Outputs and Output modules), with the exception of the NON-
Controlled Outputs (terminals [CM1-NC1-NO1] and [CM2-NC2-NO2]).
Select the SIL option from the SYSTEM
menu (press 4) to access and program the
Silence mode.
The display will show ...
Mode Select the Silence mode:
Ø Day (Default) - Silence status will be held until the SILENCE button is
pressed. The control panel will set to Day mode on power up.
Ø Night - Silence status will be held for the programmed Time ON, or until
the SILENCE button is pressed again.
Ø AUTO - Silence status will operate in Day Mode during the hours and days
programmed on the Timers (see Timer below), otherwise, it will operate in
Night Mode.
+
If an alarm condition is detected during Silence mode, the programmed
Outputs will be activated.
Time ON Enter the maximum Silence Time for Night Mode. Enter from 00.5 through
20.0 minutes with steps of 0.5 minutes. The default is 0.5 minutes (30 sec-
onds).
Timer Select the Timer for AUTO mode. Select T
or S, or T and S as required. Both Timers
are programmed by means of the Timer
option from the OPTION menu.
Press the ↵ key to confirm, or ESC to exit without saving and step back to
the SYSTEM menu.
PRG: SYSTEM
1=Date/Time 2=Blink
3=Wire 4=SIL 5=WT
6=NET 7=Printer
PRG: SYSTEM
Silencing
MODE: Night
Time ON= ØØ,5 T S
PRG: SYSTEM
Silencing
MODE: Night
Time ON= ØØ,5 T S
68 Analogue Fire Control Panel FireClass200