The warning thresholds of each loop device can be programmed individu-
ally, as follows:
Enter a value of 00 through 99% with
steps of 1%. The Warning Threshold de-
fault value is 30%.
Press the key to confirm, or ESC to exit without saving.
Alarm Verify (V)
Select the Alarm Verify option for the Verify Time. The Verify Time will
start when a device exceeds the ALARM Threshold.
If the Analogue Value is higher than the Alarm threshold when the Verify
Time expires, the control panel will generate ALARM status. However, if
the Analogue Value drops below the Alarm threshold before the end of the
Verify Time, the control panel will hold Standby status, and will increase
automatically the value of the Verify Counter of the device.
If the Analogue Value is higher than the Alarm threshold, when the Verify
Counter reaches the programmed value, the control panel will generate an
ALARM. To delete (clear) all the Verify Counters ---- select the Delete
Verify option from the MODIFYING menu.
+
If another device exceeds the ALARM threshold during the Verify Time,
the control panel will generate an instant ALARM.
Select V from the OPTION menu (press 2)
to program the Verify Time.
Select the Alarm Verify option (00.0 min-
utes at default). Enter the required value.
Accepted values: 00.0 through 20.0 min-
utes in steps of 00.5 minutes.
Press to confirm or ESC to exit without saving.
PRG:Warning thresh.
Loop: 1 M Addr. 01
Device Label
Warn: threshold:%3Ø
PRG: OPTION
Ø=P 1=W 2=V 3=D 4=T
5=S 6=H 7=D 8=Pulse
9=Extinction mode
PRG: OPTION
Alarm Verify
Verify Time: ØØ.Ømin
PROGRAMMING 59