Delay
Use the Delay option to access and program the Fixed Delay and PAS
Delay.
Fixed Delay The Fixed Delay will start when alarm conditions occur on software zones
with the Delay attribute (ON). The Fixed Delay will be signalled by blinking
on the Software Zones LED.
Press ACK to extend the running Fixed Delay. The PAS Delay (if en-
abled) will be added to the Fixed Delay.
The software zones will generate ALARM status when the total time of
both delays expires.
The Fixed Delay and PAS Delay (Positive Alarm Sequence) must be en-
abled (ON) and programmed using the D option from the OPTIONS menu.
+
If another software zone detects ALARM conditions during the delay, the
control panel will override the delay and generate an instant ALARM.
Select D from the OPTION menu (press 7)
to access the Fixed and PAS delays.
Enter the Fixed Delay and the PAS Delay
times (accepted values 0 through 20 min-
utes in steps of 0.5 minutes).
Select ON to enable the PAS Delay.
The default value is the same for both De-
lays: 2 minutes; OFF.
Press the key to confirm, or ESC to exit without saving and step back to
the previous menu.
PRG: OPTION
Ø=P 1=W 2=V 3=D 4=T
5=S 6=H 7=D 8=Pulse
9=Extinction mode
PRG: OPTION
DELAY
Fixed:ØØ,Ø PAS:****
PAS=OFF