Timer and Special Timer (T and S)
In order to lower the false alarm rate, the Alarm Threshold of analogue de-
tectors must be INCREASED during Day mode (to allow for cigarette
smoke, heaters, etc.).
The Timer can be set to activate/deactivate (ON/OFF) the Increased
Alarm Threshold value.
The Special Timer is especially useful in work places with split shifts (fac-
tories, offices, etc.).
Both Timers have exactly the same programming and operating modes.
+
Ensure that the control-panel calendar and clock are properly set.
Select T from the OPTION menu (press 4)
to access the Timer parameters.
Fig. 24 shows the respective parameters.
Select S from the OPTION menu (press 5)
to access the Special Timer parameters.
Fig. 25 shows the respective parameters.
ON Enter the time of the day (hour and minutes) when the Alarm Threshold
must be increased by the non-modifiable Default value.
OFF Enter the time of the day (hour and minutes) when the programmed Alarm
Threshold must be restored.
Days Enter the days of the week when the ON-OFF times must be applied.
PRG: OPTION
Ø=P 1=W 2=V 3=D 4=T
5=S 6=H 7=D 8=Pulse
9=Extinction mode
PRG: OPTION
Ø=P 1=W 2=V 3=D 4=T
5=S 6=H 7=D 8=Pulse
9=Extinction mode
Figure 24 Timer parameters
PROGRAMMING 61