Devices
The Device option from the PROGRAMMING menu will allow you to
change the parameters of the Devices enrolled on loops 1 and 2.
The Device option also applies to the parameters of the Conventional line
(terminal [LC]), and those of the Bell Outputs on the Main board (terminals
[Cx]) and on Expander Outputs (terminals [Cx]).
Select the Device option from the PRO-
GRAMMING menu (press 2).
If the control panel concerned is a SLAVE
the display will show ...
If the control panel concerned is the
MASTER panel the display will show ...
Select the required option and refer to the respective section.
Loop 1 and Loop 2
1. Select LOOP 1 or LOOP 2 from the DE-
VICE menu.
2. Enter the device address (for parameter
changes). Press the ↑ key to change the
Conventional Line parameters (terminal
[LC]), and refer the instructions in the
"Conventional Line" section.
3. If the entered address is valid the display
will be as shown in the "Auto learning"
section. If not, the display will show the
Device not configured message. Press
ESC to exit and go back to step 2.
1=Auto 2=Devices
3=PassWD 4=MesINI
5=Zones 6=Opt 7=Sys
8=Ver 9=Def Ø=Tel
PRG: Devices
1=LOOP 1 2=LOOP 2
3=Outputs BELL
NET not supported
PRG: devices
1=LOOP 1 2=LOOP 2
3=Outputs BELL
4=NET
PRG: Devices
1=LOOP 1 2=LOOP 2
3=Outputs BELL
4=NET
PRG: devices L1
Enter Address
Sensors L1: 1/##
Modules L1: 1/__
DEVICES LOOP1
Device not
configured
on LOOP 1
50 Analogue Fire Control Panel FireClass200