Prealarm time (P)
An input device programmed with Prealarm time will generate ALARM
status when the prealarm time elapses. Prealarm status is signalled by:
Ø an audible signal emitted by the control panel and repeater panels;
Ø blinking on the PREALARM LED;
Ø blinking on the LEDs of the associated software zones;
Ø the following message on the display (from Firmware version 4.0)
Select P from the OPTION menu (press 0)
to program the Prealarm time.
Enter values of 0.00 through 20.00 min-
utes with steps of 0.5 minutes. The default
prealarm time is 1 minute.
Press the ↵ key to confirm or ESC to exit without saving.
Warning Threshold (W)
If a loop device exceeds the preset Warning Threshold, the Control panel
will generate Warning status.
The Warning Threshold is valid for loop devices with the Warning attrib-
ute.
Select W from the OPTION menu
(press 1).
PREALARM 01/=002
FIRE CLASS 00
Device: SEN1/01
Software Zone 01
PRG: OPTION
Ø=P 1=W 2=V 3=D 4=T
5=S 6=H 7=D 8=Pulse
9=Extinction mode
PRG: OPTION
PREALARM
Enter Prealarm
time : Ø1,Ømin.
Control
Panel in
WARNING
Status !
PRG: OPTION
Ø=P 1=W 2=V 3=D 4=T
5=S 6=H 7=D 8=Pulse
9=Extinction mode
58 Analogue Fire Control Panel FireClass200