Most of the software zones parameters are described in the "Program-
ming: Fire detectors" section. The following parameters are for software
zones only.
Delay Select ON to apply the Fixed Delay and PAS Delay to the software zones.
The Fixed Delay will start when an alarm condition occurs on a software
zones with the Delay enabled (ON). The Fixed Delay will be signalled by
blinking on the software zones LED.
Press ACK to extend the running Fixed Delay - the PAS Delay (if en-
abled) will be added automatically to the Fixed Delay.
The software zones will go into ALARM status when the total time of both
delays elapses.
+
The Fixed Delay and PAS Delay (Positive Alarm Sequence) can be en-
abled, and programmed by means of the D option from the OPTIONS
menu.
OPTION
Many of the parameters can be programmed through the Opt option from
the PROGRAMMING menu.
Select the Opt option from the PRO-
GRAMMING menu.
Select the required option, in accordance
with the following table, and refer to the re-
spective section. Press ESC to step back
to the PROGRAMMING menu.
KEYS OPTIONS
0 Prealarm time
1 Warning threshold
2 Verify
3 Drift Compensation (VALUE CONTROLLED AUTOMATICALLY)
4 Timer
5 Special Timer
6 Holidays
7 Delays (Fixed and PAS)
8 Pulse
9 Extinction modes
1=Auto 2=Devices
3=PassWD 4=MesINI
5=Zones 6=Opt 7=Sys
8=Ver 9=Def Ø=Tel
PRG: OPTION
Ø=P 1=W 2=V 3=D 4=T
5=S 6=H 7=D 8=Pulse
9=Extinction mode
PROGRAMMING 57