Walk Test
The Walk Test allows the installer to check proper functioning of the Input
Points of each separate software zones. When a software zones ---- in
Walk Test status goes into ALARM status, the control panel will activate
the Alarm Outputs for a period of 1 to 15 seconds (depending on the num-
ber of detectors on the loops).
+
The Extinction Outputs will not be activated.
1. Select the WT option from the SYSTEM
menu (press 5).
2. Select ON to enable the Walk Test.
3. Select the required Zone.
4.
Press thekey to activate the Walk Test.
The Walk Test status will be signalled by:
Ø the message - WALK TEST ACTIVE ON ZONE: # (the Zone will be indi-
cated in the space filled by # in the example);
Ø Blinking on the TEST LED (0.5 second intervals);
Ø a long beep, followed by a long pause (2 second intervals).
Select OFF at step B to disable the Walk Test.
+
Test status will be abandoned automatically if any Zone, other than the
Zone in TEST status, goes into ALARM status.
+
Test status will be abandoned automatically if any type of Fault is detected.
PRG: SYSTEM
1=Date/Time 2=Blink
3=Wire 4=SIL 5=WT
6=NET 7=Printer
PRG: SYSTEM
Walk Test
Walk Test: ON
on Zone : Ø1
PRG: SYSTEM
Walk Test
Walk Test: ON
on Zone : ##
FIRE CLASS 2ØØ
WALK
TEST
ACTIVE ON ZONE: ##
PROGRAMMING 69