will stop when the control panel is RESET. The default Time ON is 0
(TMP indefinite).
The programmed Delay will start when the activating conditions specified
in the LOG (logic) parameter occur.
It is possible to stop Extinction devices whilst the Delay is running; as
specified in the Mode parameter.
When the programmed Delay elapses the Extinction devices will be acti-
vated for the programmed Time ON.
The enabled output modules and the Bell Outputs will be activated after
the programmed Delay.
They will hold the activated status for the programmed Time ON .
+
The Extinction Mode settings will be valid for the Outputs with the same
Mode type (refer to "Extinction mode" of the Output modules and Bell Out-
puts).
1. Select the Extinction Mode option from
the OPTION menu (press 9) to access and
program the Extinction Modes.
2. Select the required Extinction Mode, or
press ESC to step back to the OPTION
menu.
3. DLY is for the Delay; TMP stands for Time
ON.
4.
Press the key to confirm and go back to step 2. Press ESC to exit with-
out saving and go back to step 2.
PRG: OPTION
Ø=P 1=W 2=V 3=D 4=T
5=S 6=H 7=D 8=Pulse
9=Extinction mode
PRG: OPTION
Choose Extinction:
1= Ext1 2= Ext2
3= Ext3 4= Ext4
PRG: OPTION
Extinction M.: E#
DLY=3Ø MODE=ADD TMP
LOG=OR TMP=ØØ,Ø min
PROGRAMMING 65