Control Panel Area Wide Parameters | en 107
Bosch Security Systems, Inc. Program Entry Guide 2017.03 | 09 | F.01U.303.998
Yes – switch the arming state of the area from All On Delay to Part On Delay if no Part On
Delay points are faulted and restored during the exit delay time.
No – keep the arming state of the area All On Delay, whether or not, a Part On Delay point is
faulted and restored during the exit delay time.
This parameter selects whether or not the arming state for an area changes from All On to Part
On if no Part On Delay points are faulted during Exit Delay.
Only the final armed state is reported and displayed at the keypads.
When arming from a keyfob or SKED, the panel ignores this option.
RPS Menu Location
Area Wide Parameters > Area/Bell Parameters, Open/Close Options > All On - No Exit
4.1.33 Exit Delay Warning
Default: No
Selections:
– Yes - pulse the alarm output for the last 10 seconds of Exit Delay
– No - do not pulse the alarm output during Exit Delay
This parameter enables the alarm bell to pulse on and off every two seconds for the remaining
10 seconds of Exit Delay.
Notice!
To comply with SIA CP-01 False Alarm Reduction, set this parameter to Yes. Refer to SIA
CP-01 Verification for more information.
RPS Menu Location
Area Wide Parameters > Area/Bell Parameters, Open/Close Options > Exit Delay Warning
4.1.34 Entry Delay Warning
Default: No
Selections:
– Yes - pulse the alarm output for the last 10 seconds of Entry Delay
– No - do not pulse the alarm output during Entry Delay
When this parameter is set to Yes, the alarm bell pulses on and off every two seconds for the
remaining 10 sec of Entry Delay.
Notice!
To comply with SIA CP-01 False Alarm Reduction, set this parameter to Yes. Refer to SIA
CP-01 Verification for more information.
When upgrading a non-control panel account to a control panel account, RPS forces the
default to No.
RPS Menu Location
Area Wide Parameters > Area/Bell Parameters, Open/Close Options > Entry Delay Warning
4.1.35 Area Re-Arm Time
Default:00:00
Selections: 00:00 thru 23:59
00:00 = disabled
This parameter sets the length of time (HH:MM) that a disarmed area delays until it rearms to
All On Delay.