Control Panel Compliance Settings | en 27
Bosch Security Systems, Inc. Program Entry Guide 2017.03 | 09 | F.01U.303.998
Notice!
After system installation and any control panel programming, perform a complete system test.
A complete system test includes testing the control panel, all devices, and communication
destinations for proper operation.
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER
INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply
with the requirements in the Standard for Control Units and Accessories for Fire Alarm
Systems, UL 864, you must limit certain programming features or options to specific values.
RPS Menu Location:
Compliance Settings > UL864 Fire Application
2.4 Supervision configuration
Optimizing data used for supervision:
Installation
Type
Commercial
Burg
(UL1610)
Commercial
Burg (ULC
S304)
High
Supervision
Hourly Medium
Security or
Household
Fire
Daily
Supervision
Required
Supervision
Interval
200 sec 180 sec 300 sec 1 hr 4 hr 25 hr
Recommen
ded Service
Plan
Extended Extended High
Supervision
Standard Standard Backup
Panel Programming
Receiver
Supervision
Time
200 sec Custom 300 sec 1 hr – NFPA 4 hr –
Medium
Security
25 hr
Panel Poll
Rate (sec)
n/a 89 sec n/a n/a n/a n/a
Panel ACK
Wait (sec)
n/a 15 n/a n/a n/a n/a
Panel Retry
Count
n/a 5 n/a n/a n/a n/a