120 en | Keypads Control Panel
2017.03 | 09 | F.01U.303.998 Program Entry Guide Bosch Security Systems, Inc.
Disable when the proximity reader is not in use with the system. Disabling the credential
reader when not in use reduces power consumption. Available for the B94x Touch screen
keypads.
RPS Menu Location
Keypads > Keypad Assignments > Disable Token Reader
5.1.31 Enable Tamper Switch
Default: No
Selections:
– Yes - enable the Tamper Switch.
– No - disable the Tamper Switch.
This parameter is only supported on SDI keypads and the B915. When a legacy keypad is
selected from Keypad Type, page 110, this parameter can be modified. Otherwise it is grayed
out.
RPS Menu Location
Keypads > Keypad Assignments > Enable Tamper Switch
5.1.32 Feature Button Option
Default: Language Selection
Selections:
– Language - allows the user to switch between the first and second languages as
configured under the Panel Info tab of the Panel Data dialog box.
– Event Memory - allows the user to quickly access and view Event Memory.
This parameter sets which feature shows in the upper left corner of a B94x keypad display.
This parameter applies to B94x Touch Screen keypads only.
RPS Menu Location
Keypads > SDI2 Keypad Assignments > Feature Button Option
5.1.33 Supervision
Default:Yes
Selections:
– Yes - only one keypad can be installed for this KP# SDI address.
– No - more than one keypad can be installed using this KP# SDI address using the same
address DIP switch setting.
This parameter can be modified when an SDI keypad is selected from Keypad Type, page 110,
otherwise it is grayed out and cannot be modified. Use this parameter to supervise this SDI
address and generate TROUBLE SDI ## reports and local trouble annunciation if a problem
occurs with this keypad or the SDI bus.
Notice!
UL 864 requirement for commercial fire
To comply with UL864 requirements for commercial fire systems, set this parameter to Yes
Notice!
SDI D125xRB Fire Keypads are always supervised, even when this parameter is set to no.