44 en | Panel Wide Parameters Control Panel
2017.03 | 09 | F.01U.303.998 Program Entry Guide Bosch Security Systems, Inc.
3.8 Reporting Overview
Figure3.1: Reporting Overview
1 - Reports begin with events
The control panel monitors points, modules, keypads, and it's own power (AC and battery) for
off-normal conditions. When it detects an off-normal condition (or a restoral from an off-
normal condition), it creates an event. The control panel logs events in its history log and can
send them as reports to a central station receiver or to users as Personal Notification.
When the control panel has reports to send it first sorts them into the Route Groups (1 to 4).
Each Route Group has its own communicator, with a primary destination device, and
secondary destination device, to send the reports in the Route Group to a central station
receiver.
2 - Report Routing parameters
Use the Report Routing, page 46 parameters to configure the four Route Groups (1 to 4). The
parameters under the Report Routing heading assign reports to Route Groups by category (all
Fire Reports or all Burglar Reports for example) or individually (Fire Alarm for example).
You can assign reports to one or more Route Groups.