142 en | Output Parameters Control Panel
2017.03 | 09 | F.01U.303.998 Program Entry Guide Bosch Security Systems, Inc.
This parameter enables the output to activate when any gas supervisory point on the control
panel is in a supervisory event (off normal). A steady output is provided until all gas
supervisory points are restored to a normal condition and the event message is cleared by the
user at the keypad.
Notice!
To ensure proper operation, do not assign more than one function to the output associated
with this summary function.
Notice!
Fire/gas trouble points must be restored to normal before summary outputs can be cleared.
RPS Menu Location
Output Parameters > Panel Wide Outputs > Summary Gas Supervisory Output
8.2.14 Summary Gas Trouble Output
Default: 0
Selections:
– B9512G: 0 to 599
– B8512G: 0 to 99
This parameter sets the output to activate when any gas point on the control panel is in
trouble. A steady output is provided until all gas points have restored to a normal condition
and the event message is cleared by the user at the keypad.
Notice!
To ensure proper operation, do not assign more than one function to the output associated
with this summary function.
Notice!
Fire/gas trouble points must be restored to normal before summary outputs can be cleared.
RPS Menu Location
Output Parameters > Panel Wide Outputs > Summary Gas Trouble Output
8.3 Output Configuration
8.3.1 Output Source
Default:
– Output A(1): On-board A
– Output B(2): On-board B
– Output C(3): On-board C
– All other Outputs: Unassigned
Selections:
– On-board
– Unassigned
– Octo-output
– IP Camera