Control Panel Panel Wide Parameters | en 31
Bosch Security Systems, Inc. Program Entry Guide 2017.03 | 09 | F.01U.303.998
Selections:
– Yes - Send expanded test reports.
– No - Do not send expanded test reports.
When this parameter is set to Yes, the control panel expands test reports to include off-normal
system status information.
The control panel expands manually initiated test reports and Sked initiated (scheduled) test
reports.
RPS Menu Location
Panel Wide Parameters > Phone and Phone Parameters > Expand Test Report
3.1.9 PSTN Compatibility
Default:USA
Selections:
– USA
– Australia
– New Zealand
This parameter configures the control panel and the B430 Plug-in Telephone Communicator to
support public switched telephone networks (PSTN) in the USA, Australia, or New Zealand.
Notice!
PSTN requirement for Australia / New Zealand, disable RPS answer armed/disarmed
If you set this PSTN Compatibility parameter to Australia or New Zealand, you must set
PanelWideParameters > RPSParameters > AnswerArmed and AnswerDisarmed to 0
(disabled).
RPS Menu Location
Panel Wide Parameters > Phone and Phone Parameters > PSTN Compatibility
3.2 On Board Ethernet (IP) Communicator
3.2.1 IPv6 Mode
Default: No
Selections:
– Yes - Enable IPv6
– No - Disable IPv6 (Use IPv4 mode).
This parameter configures IP communication for IPv6 (Internet Protocol version 6) or IPv4
(Internet Protocol version 4)
When IPv6 Enable is set to Yes, the IPv4 parameters are read only (grayed out and not
editable). Set DHCP/AutoIP enable to Yes.
When IPv6 Enable is set to No, the IPv6 parameters are read only (grayed out and not
editable).
RPS Menu Locations
Panel Wide Parameters > Onboard Ethernet Communicator > IPv6 Mode,
3.2.2 IPv4 DHCP/AutoIP Enable
Default: Yes
Selections:
– Yes - enable DHCP to automatically configure the IP Address, IP Default Gateway, and IP
DNS Server Address.
– No - manually configure the IP Address, IP Default Gateway, and IP DNS Server Address.
Use this setting if there is no DHCP service.