EasyManua.ls Logo

Bosch B9512G - Module Enclosure Tamper; System (Repeater) Supervision Time; Low Battery Resound; Enable Jamming Detection

Bosch B9512G
284 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Control Panel SDI2 modules | en 253
Bosch Security Systems, Inc. Program Entry Guide 2017.03 | 09 | F.01U.303.998
14.7.2 Module Enclosure Tamper
Default: No - Disable
Selections:
Yes - Enable enclosure tamper input
No - Disable enclosure tamper input
This parameter enables the enclosure tamper switch input on the SDI2 module.
When the input is enabled and connected to a Bosch ICP-EZTS tamper switch installed in the
module enclosure, the control panel can create a tamper event when the enclosure door is
opened, or when the enclosure is removed from the wall.
RPS Menu Location
SDI2 > Wireless Receiver > Enclosure Tamper
14.7.3 System (Repeater) Supervision Time
Default: 12 hours
Selections:
– None - Disable wireless repeater supervision.
– 4, 12, 24, 48, 72 hours
This parameter sets the supervision time for all configured wireless repeaters. If the wireless
receiver does not hear from a repeater within the number of hours set by this parameter, the
control panel creates a missing repeater event.
Notice!
Wireless Point Supervision Time
Configure the wireless supervision time for non-fire points using the parameter Point
Profiles / Wireless Point Supervision Time, page 200. The wireless point supervision time for
fire points is fixed at 4 hours.
Notice!
Wireless Keyfob Supervision Time
Enable or disable wireless supervision time for wireless keyfobs using the parameter User
Assignments / Supervised, page 148. When supervision is enabled, the wireless keyfob
supervision time is fixed at 4 hours.
RPS Menu Location
SDI2 > Wireless Receiver > System Supervision Time
14.7.4 Low Battery Resound
Default: Never Resound
Selections: Never Resound, 4 hours, 24 hours
This parameter is global for all non-fire points. The control panel automatically fixes the Low
Battery Resound at 24 hours for fire points.
RPS Menu Location
SDI2 Modules > Wireless Receiver > Low Battery Resound
14.7.5 Enable Jamming Detection
Default: Yes
Selections: Yes / No
This parameter setting turns on or off the reporting of interference to the control panel.