Control Panel Points | en 205
Bosch Security Systems, Inc. Program Entry Guide 2017.03 | 09 | F.01U.303.998
Interior Follower points do not initiate entry delay even when configured for a delayed alarm
response (Point Response, page 184 set to 4, 5, 6, 7, or 8).
Notice!
Use the Interior, page 204 profile and delayed alarm response for interior points that
initiate entry delay
For some installations you may want an interior point that can initiate entry day. Tripping an
Interior point configured for delayed alarm response (refer to Point Response, page 184) while
the area is All On initiates entry delay. The alarm response is delayed until exit delay time
expires. If the area is turned Off before entry delay time expires there is no alarm response.
10.4.5 Keyswitch Maintained
Program Point Response as 1. Do not connect initiating devices to a keyswitch point.
– Normal:The area is disarmed.
– Open:When this point changes from normal to open, the area arms.
– Short:A short is a trouble while the area is disarmed. A short is an alarm while the area is
armed. When this point changes from shorted to normal or open, it restores.
If you program Point Response as 2, the point responds as follows:
– Normal:When this point changes from open to normal, the area arms.
– Open:The area is disarmed.
– Short:A short is a trouble while the area is disarmed. A short is an alarm while the area is
armed. When this point changes from shorted to normal or open, it restores.
Trouble and restoral reports are not sent if Local While Disarmed, page 194 is set to Yes.
Alarm and restoral reports are not sent if Local While Armed, page 195 is set to Yes.
Notice!
Point Response 2 is required for Inovonics FA113 Wireless devices.
10.4.6 Keyswith Momentary
Used for area arming and disarming. Point Response must be programmed 1. Do not connect
initiating devices to a keyswitch point.
– N–>S–>N:When this point momentarily changes from normal to shorted to normal, it
toggles the armed state of the area.
– Open:An open is a trouble while the point is disarmed. An open is an alarm while the
point is armed.
When this point changes from open to normal, it restores.
Trouble and restoral reports are not sent if Local While Disarmed, page 194 is set to Yes.
Trouble and restoral reports are not sent if Local While Armed, page 195 is set to Yes.
10.4.7 Open / Close Point
Used for point arming and disarming. Point Response must be programmed 1. Local bells are
silenced through the keypad.
– Normal:The point is armed and sends a POINT CLOSING. Point Closing is not sent if
Local While Armed, page 195 is set to Yes.
– Open:An open is an alarm while the point is armed. An open is a trouble while the point
is disarmed. ALARM and RESTORAL reports are not sent if Local While Disarmed, page 194
is set to Yes.