Control Panel Area Wide Parameters | en 93
Bosch Security Systems, Inc. Program Entry Guide 2017.03 | 09 | F.01U.303.998
RPS Menu Location
Area Wide Parameters > Area/Bell Parameters, Open/Close Options > Account Number.
4.1.5 Force Arm/Bypass Max
Default:2
Selections:
– B9512G: 0-99
– B8512G: 0-30
This parameter specifies the maximum number of combined controlled points that can be
faulted or in a bypassed state when arming this area.
Refer to Force Arm Returnable, page 196 and Bypass Returnable, page 196 in the Point Index for
returning a point to the system when the point returns to normal or when the area is
disarmed.
Notice!
Points must have Bypassable, page 196 set to Yes to be bypassed or force armed. Force
arming does not bypass 24-hour points.
Notice!
To comply with UL1610, set this parameter to 0 for wireless keyfobs.
RPS Menu Location
Area Wide Parameters > Area/Bell Parameters, Open/Close Options > Force Arm/Bypass Max.
4.1.6 Delay Restorals
Default:No Delay
Selections:
– No Delay. Point restoral events are logged and reported when the point physically
restores.
– Delay Until Bell Expires. Point restoral events are not logged or reported until the point
has physically restored and the bell silenced or bell time expires.
Use this parameter to delay restoral reports.
Notice!
UL 864 requirement for commercial fire
To comply with UL864 requirements for commercial fire systems, set this parameter to Yes
For Fire/Gas Alarm/Supervisory points, restoral events are not logged or reported until the
point has physically restored, the bell silenced, and the event cleared from the keypads.
RPS Menu Location
Area Wide Parameters > Area/Bell Parameters, Open/Close Options > Delay Restorals
4.1.7 Exit Tone
Default:Yes
Selections:
– Yes Sound an exit tone at all keypads during exit delay.
– No Turn off exit tones for individual keypads (based on their KP# 1 through 8).
This parameter sounds an exit tone during exit delay at all keypads assigned to this area.