Control Panel Output Parameters | en 135
Bosch Security Systems, Inc. Program Entry Guide 2017.03 | 09 | F.01U.303.998
8.1.5 Force Armed
Default:0
Selections:
– B9512G: 0 to 599
– B8512G: 0 to 99
This output activates when this area is force armed. It remains activated until the area is
disarmed or the control panel is reset. This output does not activate when Part On force
arming.
Each area can be assigned a unique output number for each of the events listed in this
section.
RPS Menu Location
Output Parameters > Area Wide Outputs > Force Armed
8.1.6 Watch Mode
Default:0
Selections:
– B9512G: 0 to 599
– B8512G: 0 to 99
This output activates when a controlled point programmed for Watch Point is tripped in the
specified area while the area is in Watch Mode and the point is not armed. It remains activated
for two seconds after each point is faulted.
Each area can be assigned a unique output number for each of the events listed in this
section.
RPS Menu Location
Output Parameters > Area Wide Outputs > Watch Mode
8.1.7 Area Armed
Default:0
Selections:
– B9512G: 0 to 599
– B8512G: 0 to 99
The output activates when the specified area becomes All On (exit delay must expire before
the output activates). The output remains activated until the area is disarmed, it does not
deactivate during the entry delay time.
If multiple areas use the same output, the output activates when all areas are armed. It
deactivates when the first area disarms.
– Keyswitch area armed status with LED's. Use an module and connect an LED to display
the armed state.
– Alternate communication trigger: This output can be used to trigger the input zone of a
device being used as a slave to report control panel arming status.
Each area can be assigned a unique output number for each of the events listed in this
section.
RPS Menu Location
Output Parameters > Area Wide Outputs > Area Armed
8.1.8 Area Off
Default: 0
Selections:
– B9512G: 0 to 599
– B8512G: 0 to 99