Commands for Level Indication
/METER /READ R Read out all actual vu and output U/I
values
Commands for Amplifier Temperature
Indication
/TEMP /MODULE R 10...137.5
[°C]
Read out actual RCM-26 temperature
/SUPPLY R 10...137.5
[°C]
Read out actual power supply
temperature (primary side)
/ATMO R 10...137.5
[°C]
Read out actual atmosphere
temperature (in chassis)
/CHAN_A /AMP R 10...137.5
[°C]
Read out actual channel A output
amplifier temperature
/
SUPPLY
R 10...137.5
[°C]
Read out actual power supply
temperature (channel A, secondary side)
/TH_HR R 0...127.5 [K] Read out thermal headroom of channel A
/
TH_TRS
/TRS R / W 20...150
[°C]
Threshold for thermal headroom
(THRM_HDRM) flag. The flag is set as
soon as the headroom falls below this
threshold.
/
TH_TRS
/HYS R / W 0...40 [°C] Hysteresis for thermal headroom
(THRM_HDRM) flag. The flag is deleted,
as soon as the headroom rise above the
threshold plus hysteresis.
/CHAN_B ... R Same as above for input channel B
/OVT_TRS /TRS R / W 20...150
[°C]
Threshold for thermal overload (OVT)
flag. The flag is set as soon as the
temperature threshold is reached by at
least one temperature value.
/HYS R / W 0...40 [°C] Hysteresis for thermal overload (OVT)
flag. The flag is deleted, as soon as the
temperature falls below the threshold
minus hysteresis.
Commands for Audio Monitoring
IRIS-Net REMOTE AMPLIFIER | en 221
Bosch Security Systems B.V. User Manual 2017.05 | 3.20 | F.01U.119.956