PVA-15CST
The PVA-15CST is a call station for the PAVIRO system. As standard, the call station has a gooseneck microphone with
pop shield and permanent monitoring, a total of 20 buttons, an illuminated LC display, and an integrated loudspeaker.
The call station can be modified to suit the user’s requirements by connecting up to five PVA-20CSE call station
extensions, each with 20 customizable selection buttons.
Other properties:
Five menu/function keys (pre-programmed) – one green or one yellow indicator light per button
15 selection buttons (customizable) – two indicator lights (green/red) per button
Label with transparent covering – the label can be changed at any time
Can be used as a standing or desk/rack flush-mounted device
Internal monitoring with error logging – complying with all relevant national and international standards
Easy configuration – use of the Configuration Wizard or IRIS-Net software
Configuration Wizard
During configuration of call-stations, the user can select inclusion (or not) of the Emergency Key Set. On inclusion,
call-stations will be preconfigured with Emergency Buttons and a Key Switch.
There is a new key included, Indicator Test key, which allows the user to start an LED test on a call-station.
The settings option for Voice Alarm (EN54-16) for a Controller is no longer available.
A new setting, Smart Safety Link, is now available with the PAVIRO wizard. Enabling it allows connecting an
FPA-5000 device to a PAVIRO controller.
PVA-15CST Device
Start by creating a PVA-15CST device in your IRIS-Net project. Drag a PVA-15CST from the Object Bar’s Devices
category or from the Devices window into the worksheet (see also chapters: Devices and Configurations menu). The
following dialog box appears:
Select the call station bus the device is connected to. A maximum of 16 CST’s is allowed per controller and a maximum
of 64 CST’s is allowed in a network.
Specify the desired number of devices, the address of the call station and number of call station extensions (it is not
possible to add extensions to a call station kit). Click on the OK button to accept these settings.
IRIS-Net
PAVIRO | en 969
Bosch Security Systems B.V. User Manual 2017.05 | 3.20 | F.01U.119.956