PAVIRO
Please note the following when using project files in different versions of IRIS-Net.
“old” IRIS-Net version “new” IRIS-Net version Updates
3.0.0 3.0.1 No updates of project file necessary.
3.0.1 3.1.0 No updates of project file necessary.
3.1.0 3.1.1 No updates of project file necessary.
3.1.1 3.1.2 No updates of project file necessary.
3.1.2 3.1.3 No updates of project file necessary.
3.1.3 3.1.4 No updates of project file necessary.
3.1.4 3.2.0 No updates of project file necessary.
LIMITS OF THE PAVIRO SYSTEM
Property
System with 1 Controller System with n Controllers
Speaker zones, in total 492 984
Controllers 4
Call stations per CST port 4 4
Call stations in total 16 n * 16
Routers in total 20 39
Amplifiers in total 50 n * 50
Task Engine blocks 1024 n * 1024
Number of messages 100 n * 100
Total length of messages 85 minutes n * 85 minutes
Audio signals in parallel 4 n * 4
Notice!
Due to security reasons, EVAC systems are not allowed to be connected to public networks or the
internet!
PVA-4CR12
The PVA-4CR12 Controller is the central paging manager for the PAVIRO system. Eight local audio inputs can be
switched to four audio outputs. A two channel message manager is integrated. The controller provides all the audio
processing, supervision and control functions for a complete PAVIRO system. A single controller supports up to 16 call
stations and 492 paging zones. The controller is equipped with 12 zones, 18 GPIs and 19 GPOs. One controller can
handle up to 2000 W loudspeaker load. Additional zones and power can be added by using up to 20 external routers
and 40 amplifiers with each 2 ✕ 500 W. The zone indicator lights on the front indicate the current status of every zone:
IRIS-Net PAVIRO | en 911
Bosch Security Systems B.V. User Manual 2017.05 | 3.20 | F.01U.119.956