CONTROLS
CST TEXT If call stations are configured for error indication, the text entered here is
indicated in the call station display if the error occurs. The maximum number of
characters is 11 when using system languages Korean or Chinese. The maximum
number of characters is 20 when using other system languages.
HINT: The meaning of the parameter %u is described at the error types below.
INTERNAL
MEMORY/DATA Memory or Read/Write error.
WATCHDOG Watchdog error of the device. This error type is logged conforming to standards,
press the CLEAR button to reset the error.
FIRMWARE The device firmware version is not compatible with the IRIS-Net version used. A
firmware update is recommended.
HARDWARE Error in the power supply or the A/D converters of the device.
TEMPERATURE Temperature overload of the device.
Temperature
control
Current temperature inside of the device (main board).
AUDIO
PROCESSING
Error during the processing of audio data.
MESSAGE
MANAGER
Error in the message manager.
INTERFACES
CAN BUS Fault condition on the CAN bus. Further details are provided in the Interface
dialog.
CST INTERFACE Fault condition on the PCA bus. Further details are provided in the Interface
dialog. The parameter %u gives the slot number of the erroneous module.
FIRE PANEL
INTERFACE
Fault condition of the fire panel interface (FPA 5000).
AUDIO NET Fault reflecting the collected error state in the AudioNet tab.
INT. ROUTER
DSP Error in the digital signal processing (DSP) of the device.
HARDWARE Hardware error.
PG / LT
TEMPERATURE
Temperature overload of the device.
GPI SUPERVISED Voltage at supervised GPI out of range.
IRIS-Net PAVIRO | en 917