LED Colour Assignments
Display modes for the büS/CANopen variant:
Displaymodesandcolourcodingcanbeswitchedtothecolourcodingontheelectronicmodule(see„Fig.
42“ on page 94)usingthe6DIPswitches.
Therefore, the following „Table6“appliestormwareversionB.02.00.00andhigher.
DIP1 DIP2 DIP3 DIP4 DIP5 DIP6 Description of the display modes of the device status LED (Top LED)
X X X X 0 0
8681“ClassicMode”:
the colour combinations for the position and error feedback are set using
DIPswitches1to4asdescribedintheBasicOperatingInstructions,chapter
“Settingcolourcombinations”–seealsochapter“21.1.1Devicespecic
LEDmode“8681ClassicMode””
1 1 1 1 1 0
Factory settings: software-congurable display mode:
displaymodeofthedevicestatusLEDcanbeselectedbyrmware:
-DevicespecicLEDmode(8681Classic0...15)–seechapter“21.1.1”
- NAMUR mode – see chapter “21.1.2”
- Valve mode – see chapter “21.1.3”
- Valve mode + errors – see chapter “21.1.4”
- Valve mode + errors + warnings (factory setting) – see chapter “21.1.5”
- Fixed colour – see chapter “21.1.6”
-(Top)LEDo(thereisnofeedbackviaTopLED)
(IntheBürkertCommunicatorthedisplaymodescanbefoundunder:
Generalsettings->Parameters->StatusLED->Mode)
PLEASE NOTE:
Hardware-conguredvalues(thatmeans:setviaDIPswitches)overwritethe
software-congureddisplaymode!
1 1 0 0 1 0 NAMUR mode:
The device status is displayed according to NAMUR NE 107 – see chapter
“21.1.2”
1 0 1 1 1 0
Valve mode:
Display of the position feedback – see chapter “21.1.3”
1 1 0 1 1 0
Valve mode + errors:
Display of the position and error feedback – see chapter “21.1.4”
1 1 1 0 1 0
Valve mode + errors + warnings:
Display of the position and error feedback as well as warnings – see chapter
“21.1.5”
X X X X X
X allothercombinations:(Top)LEDo
Table 6: Colour combinations / colour coding / display modes for Type 8681 IO-Link and büS/CANopen (DIP
switch settings available for büS/CANopen variant only)
Display modes for the IO-Link variant:
The display modes and colour coding listed in
„Table6“canonlybesetbyconguration/parameterisationof
thedevices,asnoDIPswitchesareavailable–-seeIODDobjectdescription(canbedownloadedfromthe
Bürkertwebsite,seechapter„4.3InformationandinstructionsontheInternet“.