Engineering Manual Engineer Menu 1-3
37
for at least the period specified by Abort Delay (page 59). If you deselect this option, any
user whose code is assigned to the ward can reset the unconfirmed alarm. See also the
Remote Reset attribute (page 37).
03 – Tamper Reset
If you select this attribute, an engineer or remote reset code must be entered to reset the
system after a tamper alarm occurs at a zone in the selected wards while the system is
unset. If you deselect this option, any user who has access to the ward can reset the
alarm. See also the Remote Reset attribute (page 37).
04 – Remote Reset
This is relevant only if the Conf reset, Unconf Reset or Tamper Reset attribute is set (see
above). The Remote Reset attribute enables the panel to generate a code when
resetting the system after an alarm in the selected wards. The user contacts an Alarm
Receiving Centre (ARC) with the code, who (if satisfied with the caller's authority) return a
one-off remote reset code, which the user enters to reset the panel. The User's Guide
describes how to enter the remote reset code.
The algorithm used to generate the remote reset code is determined by the Reset Alg
option (page 61).
05 – Panel Tamper
The control panel lid tamper can be assigned to any combination of wards. If a panel
tamper occurs, keypads in the same ward will sound (see page 26), and Tamper outputs
associated with the same ward (see page 53) will activate.
See also Tampers as Tampers/Alarms (page 79).
06 – Panel Speaker
The control panel speaker can be assigned to any combination of wards. Assigning the
speaker to the correct wards ensures that the sounders operate only when the relevant
ward(s) require a sound (e.g. for an alarm, entry or exit sound).
07 – Bell Tamp
The auxiliary and bell box tamper input can be assigned to any combination of wards. If
a panel tamper occurs, keypads in the same ward will sound (see page 26), and
Tamper outputs associated with the same ward (see page 53) will activate.
See also Tampers as Tampers/Alarms (page 79).
08 – Payment Timer
The payment timer can be assigned to any combination of wards. When the Payment
Time (page 61) expires, the selected wards will require an engineer or remote reset (see
the User's Guide) before the wards can be set.
09 – Re-arms
If you select this attribute, the ward can rearm zones that have been triggered, but which
are now no longer in the alarm state at the end of the Bell Duration time (page 57). The
number of times the zone can rearm is specified by the No. of Rearms timer (page 60).
This attribute applies only if Confirmation Off is selected (page 77).
10 – Secure Ward
A Secure ward attempts to stay in a set condition. If the ward is unset, a "Hi Security Zone
Is Unset" alert message is displayed and the Hi Security timer starts (page 61). The timer