Engineering Manual Engineer Menu 1-4
47
047 – Panel Lid Tamper
Activates when the panel lid tamper is activated; deactivates when the alarm is reset.
048 – Chime Mimic
Activates for 2 seconds when any zone with a Chime Tone attribute (page 31) is
activated, if chimes are enabled in User option 1-5.
049 – Monitored O/P On
If the output is latched, the output activates when a zone that has the Monitored
attribute (page 32) is activated and deactivates when the zone deactivates. If the output
is pulsed, it activates when a zone that has the Monitored attribute activates and remains
active for the pulse duration.
050 – Alarm Abort
Activates after an alarm has been aborted by the user; deactivates when the Abort
Period timer (page 59) has expired, or when the alarm is reset (whichever occurs first).
051 – Rem Call Enabled
Not used.
052 – Relearn Required
Activates when the system needs an engineer to confirm the devices attached to the
panel's network ports (e.g. after a new device is attached); deactivates when the relearn
has been performed.
053 – Always On
Active at all times.
054 – Always Off
This output never activates.
055 – Battery Test On
Activates during a battery test. The test starts when an engineer logs out, and lasts for
approximately 10 seconds. If required, the output can be used by the battery test input
of a monitored power supply, such as a 519.
056 – Battery Fault
Activates when the backup battery in the panel is not charging or has a low voltage.
057 – PSU - Battery
Activates while a PSU Battery zone (page 29) is active.
058 – PSU - Fuse
Activates while a PSU Fuse zone (page 29) is active.
059 – PSU - Power
Activates while a PSU Power zone (page 29) is active.
060 – General Fault
Activates when there is a general fault. A general fault occurs if one of the following
occurs.
Mains fail
PSU Battery zone (page 29) active