Engineering Manual Engineer Menu 2-5
93
The Restore Signals option in Engineer 2-5-2-5 (page 97) determines whether
restore messages are sent to the ARC.
The Tampers As Alarm/Tamps option in Engineer 1-9-3 (page 79) determines
whether tamper conditions are sent as event code 130 or 137.
The following table shows the event s that are transmitted to the ARC, depending on the
reporting level set in option 2-5-2-6 (page 98).
Event Type Event Code Basic Summary Intermediate Full
A/C Lost 301 Y Y Y
A/C Restore 301 Y Y Y
Alarm Abort 406 Y Y Y
Alarm Confirm 139 Y Y Y Y
AntiMask Alarm 380 Y Y Y
Battery Fault 311 Y Y Y
Battery Missing 311 Y Y Y
Battery Restore 311 Y Y Y
Bell Tamper Omit 573 Y Y Y Y
Code Changed 461 Y
Code Tamper 461 Y
Download Start 412 Y
Download Fail 412 Y
Download Success 412 Y
Expander Tamper 137 Y Y Y Y
Fire 110 Y Y Y Y
Fire Restore 110 Y Y Y Y
Keyswitch Arm 409 Y Y
Keyswitch Disarm 409 Y Y
Node Tamper Omit 573 Y Y Y Y
PA Audible 123 Y Y Y Y
PA Duress 121 Y Y Y Y
PA Panic 120 Y Y Y Y
PA Panic Restore 120 Y Y Y Y
PA Silent 121 Y Y Y Y
Panel Arm 401 Y Y
Panel Disarm 401 Y Y
Panel Tamper Omit 573 Y Y Y Y
Phone Line Fault 351 Y Y Y Y
Phone Line Restore 351 Y Y Y Y
Program Mode End 628 Y
Program Mode Start 627 Y
System Reset 305 Y Y Y
System Tamper 137 Y Y Y Y
System Tamper Restore 137 Y Y Y Y
Technical Alarm 150 Y Y Y Y
Test Call 602 Y Y Y Y
Time/Date Reset 625 Y
Zone Alarm 130 Y Y Y Y
Zone Restore 130 Y Y Y Y
Zone Omitted 573 Y Y Y Y
Zone Tamper 137 Y Y Y Y
Zone Tamper Restore 137 Y Y Y Y
Ward Arm 409 Y Y
4 to 7 – SIA 1, SIA 2, SIA 3 and Extended SIA 3
The SIA formats automatically transmit data from the event log to the ARC. The four SIA
formats differ in the amount of data transmitted with each message: