Engineer Menu 2-5 Engineering Manual
94
SIA1 format is: #AAAAAA|NCCcc
SIA2 format is: #AAAAAA|Nidnnn/rinn/CCcc
SIA3 format is: #AAAAAA|Ntihh:mm/idnnn/rinn/CCcc
#AAAAAA|AS
Extended SIA 3 format is: #AAAAAA|Ntihh:mm/idnnn/rinn/CCcc/AS
Where:
AAAAAA = 6-digit programmable account code (e.g. 123456), as specified in
option 2-5-2-3 (page 96).
N = New Event (always N).
tihh:mm/ = time (e.g. ti10:23/).
idnnn/ = user number, if applicable; otherwise not sent (e.g. id123/ or id6/).
rinn/ = ward no. (e.g. ri12/ or ri3).
CC = event code (e.g. FA = Fire Alarm).
cc = zone or keypad number, if applicable; otherwise not sent (e.g. 23 or 5).
AS = text description of event.
For example, if there is a fire alarm on zone 2 of ward 6 at 10:15 (ward 6 account
number is 10), the message would be:
SIA1: #000010|NFA2
SIA2: #000010|NFA2/ri6
SIA3: #000010|Nti10:15/FA2/ri6
#000010|AFire Zone 6
Extended SIA3: #000010|Nti10:15/FA2/ri6/AFire Zone 6
The following table shows the events that are transmitted to the ARC, depending on the
reporting level set in option 2-5-2-6 (page 98).
A Custom option can be selected in option 2-5-2-6; this allows the events
transmitted to be selected using Downloader.
Event Type SIA Code Basic Summary Intermediate Full
A/C Lost AT Y Y Y
A/C Restore AR Y Y Y
Alarm Abort BC Y Y Y
Alarm Confirm BV Y Y Y Y
AntiMask Alarm BT Y Y Y
Aux Restore YQ Y Y Y
Aux Trouble YP Y Y Y
Battery Fault YT Y Y Y
Battery Missing YM Y Y Y
Battery Restore YR Y Y Y
Bell Tamper Omit BB Y Y Y Y
Closing Extended CE Y
Code Changed JV Y
Code Tamper JA Y
Download Start RB Y
Download Fail RU Y