Index
Parameter
Min
Max
Unit
Default
ID
Description
P3.9.1.14
Response to Safe Torque Off
(STO) Fault
0
2
2
775
0 = No action
1 = Alarm
2 = Fault (Stop by coasting)
P3.9.1.17
Fieldbus Communication
Fault Force Delay
0.00
320.00
s
0.00
751
P3.9.1.18
Fieldbus Communication
Fault Clear Delay
0.00
320.00
s
0.00
752
P3.9.1.19
Unbalance Current Alarm
0
1
1
753
Table 58: Motor Thermal Protection Settings
Index
Parameter
Min
Max
Unit
Default
ID
Description
P3.9.2.1
Motor Thermal Protection
0
3
2
704
0 = No action
1 = Alarm
2 = Fault (Stop by stop mode)
3 = Fault (Stop by coasting)
P3.9.2.2
Ambient Temperature
-20.0
100.0
°C
40.0
705
P3.9.2.3
Zero Speed Cooling Factor
5.0
150.0
%
Varies
706
P3.9.2.4
Motor Thermal Time Constant
1
200
min
15
707
P3.9.2.5
Motor Thermal Loadability
10
150
%
100
708
Table 59: Motor Stall Protection Settings
Index
Parameter
Min
Max
Unit
Default
ID
Description
P3.9.3.1
Motor Stall Fault
0
3
0
709
0 = No action
1 = Alarm
2 = Fault (Stop according to stop mode)
3 = Fault (Stop by coasting)
P3.9.3.2
Stall Current
0.00
Is
A
Varies
710
P3.9.3.3
Stall Time Limit
1.00
120.00
s
15.00
711
P3.9.3.4
Stall Frequency Limit
1.00
P3.3.1.2
Hz
25.00
712
Table 60: Motor Underload Protection Settings
Index
Parameter
Min
Max
Unit
Default
ID
Description
P3.9.4.1
Underload Fault
0
3
0
713
0 = No action
1 = Alarm
2 = Fault (Stop according to stop
mode)
AB298035655957en-000201 / DPD01083106 | Danfoss A/S © 2023.08
Parameters Menu
VACON® 100 FLOW
Application Guide