Parameter
Min
Max
Unit
Default
ID
Description
P3.13.2.3
Setpoint ramp time
0.00
300.0
s
0.00
1068
P3.13.2.4
PID setpoint boost activa-
tion
Varies
Varies
DigIN Slot0.1
1046
OPEN = No boost
CLOSED = Boost
P3.13.2.5
PID select setpoint
Varies
Varies
DigIN Slot0.1
(1)
1047
OPEN = Setpoint 1
CLOSED = Setpoint 2
P3.13.2.6
Setpoint source 1 selection
0
32
3
(1)
332
0 = Not used
1 = Keypad setpoint 1
2 = Keypad setpoint 2
3 = AI1
4 = AI2
5 = AI3
6 = AI4
7 = AI5
8 = AI6
9 = ProcessDataIn1
10 = ProcessDataIn2
11 = ProcessDataIn3
12 = ProcessDataIn4
13 = ProcessDataIn5
14 = ProcessDataIn6
15 = ProcessDataIn7
16 = ProcessDataIn8
17 = Temperature input 1
18 = Temperature input 2
19 = Temperature input 3
20 = Temperature input 4
21 = Temperature input 5
22 = Temperature input 6
23 = Block Out.1
24 = Block Out.2
25 = Block Out.3
26 = Block Out.4
27 = Block Out.5
28 = Block Out.6
29 = Block Out.7
30 = Block Out.8
31 = Block Out.9
32 = Block Out.10
P3.13.2.7
Setpoint 1 minimum
-200.00
200.00
%
0.00
1069
P3.13.2.8
Setpoint 1 maximum
-200.00
200.00
%
100.00
1070
P3.13.2.9
Setpoint 1 boost
-2.0
2.0
x
1.0
1071
P3.13.2.10
Setpoint source 2 selection
0
Varies
2
(1)
431
See P3.13.2.6.
AB298035655957en-000201 / DPD01083114 | Danfoss A/S © 2023.08
Parameters Menu
VACON® 100 FLOW
Application Guide