P3.13.2.11
Setpoint 2 minimum
-200.00
200.00
%
0.00
1073
See P3.13.2.7.
P3.13.2.12
Setpoint 2 maximum
-200.00
200.00
%
100.00
1074
See P3.13.2.8.
P3.13.2.13
Setpoint 2 boost
-2.0
2.0
x
1.0
1078
See P3.13.2.9.
1
The selection of the application with parameter P1.2 Application gives the default value. See the default values in 11.25 Default Values of Parame-
ters in the Different Applications.
Table 77: Feedback Settings
Index
Parameter
Min
Max
Unit
Default
ID
Description
P3.13.3.1
Feedback Func-
tion
1
9
1
(1)
333
1 = Only Source1 in use
2 = SQRT(Source1); (Flow=Constant x SQRT(Pressure))
3 = SQRT(Source1- Source 2)
4 = SQRT(Source 1) + SQRT (Source 2)
5 = Source 1 + Source 2
6 = Source 1 - Source 2
7 = MIN (Source 1, Source 2)
8 = MAX (Source 1, Source 2)
9 = MEAN (Source 1, Source 2)
P3.13.3.2
Feedback Func-
tion Gain
-1000.0
2100.0
%
100.0
1058
P3.13.3.3
Feedback 1
Source Selection
0
30
2
(1)
334
0 = Not used
1 = AI1
2 = AI2
3 = AI3 4 = AI4
5 = AI5 6 = AI6
7 = ProcessDataIn1
8 = ProcessDataIn2
9 = ProcessDataIn3
10 = ProcessDataIn4
11 = ProcessDataIn5
12 = ProcessDataIn6
13 = ProcessDataIn7
14 = ProcessDataIn8
15 = Temperature input 1
16 = Temperature input 2
17 = Temperature input 3
18 = Temperature input 4
19 = Temperature input 5
20 = Temperature input 6
21 = Block Out.1
22 = Block Out.2
23 = Block Out.3
24 = Block Out.4
25 = Block Out.5
26 = Block Out.6
27 = Block Out.7
AB298035655957en-000201 / DPD01083 | 115Danfoss A/S © 2023.08
Parameters Menu
VACON® 100 FLOW
Application Guide

Table of Contents