Index
Parameter
Min
Max
Unit
De-
fault
ID
Description
3 = bar
4 = Pa
5 = kPa
6 = PSI
7 = mmHg
8 = Torr
9 = lb/in
2
P3.13.9.4
Supervision Unit
Decimals
0
4
2
1688
P3.13.9.5
Supervision Unit
Minimum Value
-99999.99
99999.99
P3.13.9.3
0.00
1689
P3.13.9.6
Supervision Unit
Maximum Value
-99999.99
99999.99
P3.13.9.3
10.0
1690
P3.13.9.7
Supervision Alarm
Level
P3.13.9.5
P3.13.9.6
P3.13.9.3
Varies
1691
P3.13.9.8
Supervision Fault
Level
P3.13.9.5
P3.13.9.7
P3.13.9.3
0.10
1692
P3.13.9.9
Supervision Fault
Delay
0.00
60.00
s
5.00
1693
P3.13.9.10
PID Setpoint Re-
duction
0.0
100.0
%
10.0
1694
P3.13.9.11
Setpoint Red Inter-
polation Source
0
2
0
1407
0 = Feedback
1 = Input pressure monitor
2 = Disabled
V3.13.9.12
Input Pressure
P3.13.9.5
P3.13.9.6
P3.13.9.3
Varies
1695
This monitoring value shows the actual
value of the pump input pressure.
Table 84: Sleep - No Demand Detected
Index
Parameter
Min
Max
Unit
Default
ID
Description
P3.13.10.1
Sleep NoDemand Detection Enable
0
1
0
1649
0 = No
1 = Yes
P3.13.10.2
SNDD Error Hysteresis
0
99999.9
P3.13.1.4
0.5
1658
P3.13.10.3
SNDD FrequencyHysteresis
0.00
P3.3.1.2
Hz
3.00
1663
P3.13.10.4
SNDD Supervision Time
0
600
s
120
1668
P3.13.10.5
SNDD Actual Add
0.00
P3.13.10.2
P3.13.1.4
0.5
1669
AB298035655957en-000201 / DPD01083 | 119Danfoss A/S © 2023.08
Parameters Menu
VACON® 100 FLOW
Application Guide

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VACON 100 FLOW Series and is the answer not in the manual?

Danfoss VACON 100 FLOW Series Specifications

General IconGeneral
BrandDanfoss
ModelVACON 100 FLOW Series
CategoryDC Drives
LanguageEnglish

Related product manuals