Parameter
Min
Max
Unit
Default
ID
Description
3 = Enabled (weekdays)
P3.21.1.2
Cleaning Activation
DigINSlot0.1
1715
P3.21.1.3
Cleaning Current Limit
0.0
200.0
%
120.0
1712
P3.21.1.4
Cleaning CurrentDelay
0.0
300.0
s
60.0
1713
P3.21.1.5
Cleaning Weekdays
0
127
0
1723
B0 = Sunday
B1 = Monday
B2 = Tuesday
B3 = Wednesday
B4 = Thursday
B5 = Friday
B6 = Saturday
P3.21.1.6
Cleaning Time of Day
00:00:00
23:59:59
00:00:00
1700
P3.21.1.7
Cleaning Cycles
1
100
5
1716
P3.21.1.8
Clean Forward Frequency
0.00
50.00
Hz
45.00
1717
P3.21.1.9
Clean Forward Time
0.00
320.00
s
2.00
1718
P3.21.1.10
Clean Reverse Frequency
0.00
50.00
Hz
45.00
1719
P3.21.1.11
Clean Reverse Time
0.00
320.00
s
0.00
1720
P3.21.1.12
Cleaning Acceleration Time
0.1
300.0
s
0.1
1721
P3.21.1.13
Cleaning Deceleration Time
0.1
300.0
s
0.1
1722
Table 100: Jockey Pump Parameters
Index
Parameter
Min
Max
Unit
Default
ID
Description
P3.21.2.1
Jockey Function
0
2
0
1674
0 = Not used
1 = PID sleep
2 = PID sleep (level)
P3.21.2.2
Jockey Start Level
Varies
Varies
Varies
0.00
1675
P3.21.2.3
Jockey Stop Level
Varies
Varies
Varies
0.00
1676
Table 101: Priming Pump Parameters
Index
Parameter
Min
Max
Unit
Default
ID
Description
P3.21.3.1
Priming Function
0
1
0
1677
0 = Disabled
1 = Enabled
P3.21.3.2
Priming Time
0.0
320.00
3.0
1678