Table 102: Anti-blocking Parameters
Index
Parameter
Min
Max
Unit
Default
ID
Description
P3.21.4.1
Anti-blocking Interval
0
96.0
h
0
1696
P3.21.4.2
Anti-blocking run-time
0
300
s
20
1697
P3.21.4.3
Anti-blocking frequency
P3.3.1.1
P3.3.1.2
Hz
15.0
1504
Table 103: Frost Protection Parameters
Index
Parameter
Min
Max
Unit
De-
fault
ID
Description
P3.21.5.1
Frost Protec-
tion
0
1
0
1704
0 = Disabled
1 = Enabled
P3.21.5.2
Temperature
Signal
0
29
6
1705
0 = Temperature Input1 (-50...200° C)
1 = Temperature Input2 (-50...200° C)
2 = Temperature Input3 (-50...200° C)
3 = Temperature Input4 (-50...200° C)
4 = Temperature Input5 (-50...200° C)
5 = Temperature Input6 (-50...200° C)
6 = Analog input 1
7 = Analog input 2
8 = Analog input 3
9 = Analog input 4
10 = Analog input 5
11 = Analog input 6
12 = ProcessDataIn1 (0–100%)
13 = ProcessDataIn2 (0–100%)
14 = ProcessDataIn3 (0–100%)
15 = ProcessDataIn4 (0–100%)
16 = ProcessDataIn5 (0–100%)
17 = ProcessDataIn6 (0–100%)
18 = ProcessDataIn7 (0–100%)
19 = ProcessDataIn8 (0–100%)
20 = Block Out.1
21 = Block Out.2
22 = Block Out.3
23 = Block Out.4
24 = Block Out.5
25 = Block Out.6
26 = Block Out.7
27 = Block Out.8
28 = Block Out.9
29 = Block Out.10
P3.21.5.3
Temperature
SignalMini-
mum
-50.0 (°C)
P3.21.5.4.4
°C/°F
-50.0
(°C)
1706
P3.21.5.4
Temperature
SignalMaxi-
mum
P3.21.5.3
200.0 (°C)
°C/°F
200.0
(°C)
1707
AB298035655957en-000201 / DPD01083 | 129Danfoss A/S © 2023.08
Parameters Menu
VACON® 100 FLOW
Application Guide

Table of Contents

Related product manuals