C
B
A
D
0 mA 20 mA10 mA
[Hz]
[%]
e30bg487.10
Illustration 57: The Analog Input Signal Range, Selection 0
A
Frequency reference
B
Max freq reference
C
Min freq reference
D
Analog input signal
0% 100%50%20%
C
B
A
D
[Hz]
[%]
0 mA 20 mA
10 mA
4 mA
e30bg488.10
Illustration 58: The Analog Input Signal Range, Selection 1
A
Frequency reference
B
Max freq reference
C
Min freq reference
D
Analog input signal
11.7.5.4 (ID 380) AI1 Custom. MIN
Location in the menu: P3.5.2.1.4
Use this parameter to adjust the range of the analog input signal between -160% and 160%.
11.7.5.5 (ID 381) AI1 Custom. MAX
Location in the menu: P3.5.2.1.5
Use this parameter to adjust the range of the analog input signal between -160% and 160%.
Use the analog input signal, for example, as frequency reference, and set the parameters P3.5.2.1.4 and P3.5.2.1.5 between 40 and
80%. In these conditions, the frequency reference changes between the Minimum frequency reference and the Maximum frequen-
cy reference, and the analog input signal changes between 8 and 16 mA.