11.7.7.2 (ID 10051) AO1 Filter Time
Location in the menu: P3.5.4.1.2
Use this parameter to set the filtering time for the analog signal. The filtering function is disabled when the filtering time is 0. See
P3.5.2.1.2.
11.7.7.3 (ID 10052) AO1 Minimum
Location in the menu: P3.5.4.1.3
Use this parameter to change the range of the analog output signal. For example, if '4 mA' is selected, the range of analog output
signal is 4...20 mA. Select the signal type (current/voltage) with the DIP switches. The analog output scaling is different in P3.5.4.1.4.
See also P3.5.2.1.3.
11.7.7.4 (ID 10053) AO1 Minimum Scale
Location in the menu: P3.5.4.1.4
Use this parameter to scale the analog output signal. The scaling values (min and max) are given in the process unit specified by the
selection of the AO function.
11.7.7.5 (ID 10054) AO1 Maximum Scale
Location in the menu: P3.5.4.1.5
Use this parameter to scale the analog output signal. The scaling values (min and max) are given in the process unit specified by the
selection of the AO function.
Select, for example, the output frequency of the drive for the contents of the analog output signal, and set parameters P3.5.4.1.4
and P3.5.4.1.5 between 10 and 40 Hz. Then the output frequency of the drive changes between 10 and 40 Hz, and the analog out-
put signal changes between 0 and 20 mA.
Illustration 62: Scaling of the AO1 Signal
AB298035655957en-000201 / DPD01083214 | Danfoss A/S © 2023.08
Parameter Descriptions
VACON® 100 FLOW
Application Guide