A
Analog output signal
B
Analog output minimum scale
C
Analog output maximum scale
D
Maximum frequency reference
E
Output frequency
11.8 Fieldbus Data
11.8.1 (ID 852) FB DataOut 1 Selection
Location in the menu: P3.6.1
Use this parameter to select the data that is sent to the fieldbus with the ID number of the parameter or monitor value.
The data is scaled to an unsigned 16-bit format according to the format on the control panel. For example, value 25.5 on the display
equals 255.
11.8.2 (ID 853) FB DataOut 2 Selection
Location in the menu: P3.6.2
Use this parameter to select the data that is sent to the fieldbus with the ID number of the parameter or monitor value.
The data is scaled to an unsigned 16-bit format according to the format on the control panel. For example, value 25.5 on the display
equals 255.
11.8.3 (ID 854) FB DataOut 3 Selection
Location in the menu: P3.6.3
Use this parameter to select the data that is sent to the fieldbus with the ID number of the parameter or monitor value.
The data is scaled to an unsigned 16-bit format according to the format on the control panel. For example, value 25.5 on the display
equals 255.
11.8.4 (ID 855) FB DataOut 4 Selection
Location in the menu: P3.6.4
Use this parameter to select the data that is sent to the fieldbus with the ID number of the parameter or monitor value.
The data is scaled to an unsigned 16-bit format according to the format on the control panel. For example, value 25.5 on the display
equals 255.
11.8.5 (ID 856) FB DataOut 5 Selection
Location in the menu: P3.6.5
Use this parameter to select the data that is sent to the fieldbus with the ID number of the parameter or monitor value.
The data is scaled to an unsigned 16-bit format according to the format on the control panel. For example, value 25.5 on the display
equals 255.
11.8.6 (ID 857) FB DataOut 6 Selection
Location in the menu: P3.6.6
Use this parameter to select the data that is sent to the fieldbus with the ID number of the parameter or monitor value.
The data is scaled to an unsigned 16-bit format according to the format on the control panel. For example, value 25.5 on the display
equals 255.
11.8.7 (ID 858) FB DataOut 7 Selection
Location in the menu: P3.6.7
Use this parameter to select the data that is sent to the fieldbus with the ID number of the parameter or monitor value.
The data is scaled to an unsigned 16-bit format according to the format on the control panel. For example, value 25.5 on the display
equals 255.
11.8.8 (ID 859) FB DataOut 8 Selection
Location in the menu: P3.6.8
Use this parameter to select the data that is sent to the fieldbus with the ID number of the parameter or monitor value.
AB298035655957en-000201 / DPD01083 | 215Danfoss A/S © 2023.08
Parameter Descriptions
VACON® 100 FLOW
Application Guide