11.12.4 (ID 718) Trial Time
Location in the menu: P3.10.4
Use this parameter to set the trial time for the automatic reset function. During the trial time, the automatic reset function tries to
reset the faults that occur.
The time count starts from the first automatic reset. The next fault starts the trial time count again.
11.12.5 (ID 759) Number of Trials
Location in the menu: P3.10.5
Use this parameter to set the total number of auto reset trials. If the number of trials during the trial time is more than the value of
this parameter, a permanent fault shows. If not, the fault goes out of view after the trial time is completed. The fault type does not
affect the maximum number of trials.
Fault trigger
Autoreset
Trial time
Wait
time
Wait
time
Wait
time
ID717
Reset 1
Reset 2
Trial time
ID718
Fault active
Alarm
Number of trials: (ID759 = 2)
ID717
ID717
e30bg301.10
Illustration 72: The Automatic Reset Function
11.12.6 (ID 720) Autoreset: Undervoltage
Location in the menu: P3.10.6
Use this parameter to enable the automatic reset after an undervoltage fault.
11.12.7 (ID 721) Autoreset: Overvoltage
Location in the menu: P3.10.7
Use this parameter to enable the automatic reset after an overvoltage fault.
11.12.8 (ID 722) Autoreset: Overcurrent
Location in the menu: P3.10.8
Use this parameter to enable the automatic reset after an overcurrent fault.
11.12.9 (ID 723) Autoreset: AI Low
Location in the menu: P3.10.9
Use this parameter to enable the automatic reset after a fault caused by low AI signal.