11.12.10 (ID 724) Autoreset: Unit Overtemperature
Location in the menu: P3.10.10
Use this parameter to enable the automatic reset after a fault caused by unit overtemperature.
11.12.11 (ID 725) Autoreset: Motor Overtemperature
Location in the menu: P3.10.11
Use this parameter to enable the automatic reset after a fault caused by motor overtemperature.
11.12.12 (ID 726) Autoreset: External Fault
Location in the menu: P3.10.12
Use this parameter to enable the automatic reset after an external fault.
11.12.13 (ID 738) Autoreset: Underload Fault
Location in the menu: P3.10.13
Use this parameter to enable the automatic reset after an underload fault.
11.12.14 (ID 776) Autoreset: PID Supervision Fault
Location in the menu: P3.10.14
Use this parameter to enable the automatic reset after a PID supervision fault.
11.12.15 (ID 777) Autoreset: EXT PID Supervision Fault
Location in the menu: P3.10.15
Use this parameter to enable the automatic reset after an external PID supervision fault.
11.12.16 (ID 1569) Fault Simulation
Location in the menu: P3.10.16
With this parameter it is possible to simulate the different faults without them being actually active. For example simulating an over
current situation. In the drive interface point of view the behavior is identical to actual fault situations.
Output phase supervision fault (F11)
Over temperature warning (W14)
Over temperature fault (F14)
(1)
1
The warning bit needs to be high also for this fault simulation to work.
AB298035655957en-000201 / DPD01083 | 231Danfoss A/S © 2023.08
Parameter Descriptions
VACON® 100 FLOW
Application Guide