Danfoss VACON 100 FLOW Series - Page 47

Danfoss VACON 100 FLOW Series
334 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
e30bj006.10
1
6
2
3
4
5
18
19
30
12
7
13
8
9
10
14
15
16
21
22
23
11
17
A
B
24
25
26
28
29
32
33
*)
**)
+
-
TI1+
TI1-
mA
FAULT
RUN
RUN
AO1-
+24 Vin
Actual value
GND
GND
DI1
DI2
DI3
DI4
DI5
DI6
RO1/1 NC
RO1/2 CM
RO1/3 NO
CM
CM
RS485
RS485
RO2/1 NC
RO2/2 CM
RO2/3 NO
Standard I/O board
Terminal Signal Description
+10 Vref
AI1+
AI1-
AI2+
AI2-
24 Vout
24 Vout
Reference output
Analog input 1 +
Analog input 1 -
Analog input 2 +
Analog input 2 -
24 V auxiliary voltage
I/O ground
Digital input 1
Digital input 2
Digital input 3
Digital input 4
Digital input 5
Digital input 6
Common for DI1-DI6
Common for DI1-DI6
24 V auxiliary voltage
I/O ground
Analog output 1 +
Analog output 1 -
24 V auxiliary
input voltage
Output
frequency
(0...20 mA)
Serial bus, negative
Serial bus, positive
Relay output 1
Relay output 2
RO3/2 CM
RO3/3 NO
READY
Relay output 3
FAULT
Fault reset
External Fault
AO1+
Not in use by default
(default: 0...10 V)
PID feedback
(actual value)
(Default 4...20 mA)
Start forward
Flushing
(StartForward + Flushing Freg.)
PID Setpoint Selection
(Open =Keypad SP1, Closed =Keypad SP2)
Pump Interlock
(Open=Not Available, Closed =Available)
Drive-to-Drive
Communication
(Modbus RTU )
2-wire transducer
To terminal
A on other
drives
To terminal
B on other
drives
(0)4...20 mA
Thermistor input
Illustration 18: The Default Control Connections of the Multi-pump (Multidrive) Application
*) Available only in VACON
®
100 X. **) For the DIP switch configurations in VACON
®
100 X, see the VACON
®
100 X Installation man-
ual.
AB298035655957en-000201 / DPD01083 | 47Danfoss A/S © 2023.08
Applications
VACON® 100 FLOW
Application Guide