e30bj006.10
1
6
2
3
4
5
18
19
30
12
7
13
8
9
10
14
15
16
21
22
23
11
17
A
B
24
25
26
28
29
32
33
*)
**)
+
-
TI1+
TI1-
mA
FAULT
RUN
RUN
AO1-
+24 Vin
Actual value
GND
GND
DI1
DI2
DI3
DI4
DI5
DI6
RO1/1 NC
RO1/2 CM
RO1/3 NO
CM
CM
RS485
RS485
RO2/1 NC
RO2/2 CM
RO2/3 NO
Standard I/O board
Terminal Signal Description
+10 Vref
AI1+
AI1-
AI2+
AI2-
24 Vout
24 Vout
Reference output
Analog input 1 +
Analog input 1 -
Analog input 2 +
Analog input 2 -
24 V auxiliary voltage
I/O ground
Digital input 1
Digital input 2
Digital input 3
Digital input 4
Digital input 5
Digital input 6
Common for DI1-DI6
Common for DI1-DI6
24 V auxiliary voltage
I/O ground
Analog output 1 +
Analog output 1 -
24 V auxiliary
input voltage
Output
frequency
(0...20 mA)
Serial bus, negative
Serial bus, positive
Relay output 1
Relay output 2
RO3/2 CM
RO3/3 NO
READY
Relay output 3
FAULT
Fault reset
External Fault
AO1+
Not in use by default
(default: 0...10 V)
PID feedback
(actual value)
(Default 4...20 mA)
Start forward
Flushing
(StartForward + Flushing Freg.)
PID Setpoint Selection
(Open =Keypad SP1, Closed =Keypad SP2)
Pump Interlock
(Open=Not Available, Closed =Available)
Drive-to-Drive
Communication
(Modbus RTU )
2-wire transducer
To terminal
A on other
drives
To terminal
B on other
drives
(0)4...20 mA
Thermistor input
Illustration 18: The Default Control Connections of the Multi-pump (Multidrive) Application
*) Available only in VACON
®
100 X. **) For the DIP switch configurations in VACON
®
100 X, see the VACON
®
100 X Installation man-
ual.
AB298035655957en-000201 / DPD01083 | 47Danfoss A/S © 2023.08
Applications
VACON® 100 FLOW
Application Guide