C
e30bg589.10
Illustration 19: The DIP Switch
A
Digital input DIP switch
B
Floating
C
Connected to GND (Default)
Each drive has a pressure sensor. When the redundancy level is high, the drive and the pressure sensors are redundant.
If there is a drive failure, the next drive starts to operate as master.
If there is a sensor failure, the next drive (that has a separate sensor) starts to operate as master.
An individual switch that has an auto, off and man setting controls each drive.